Factors affecting electricity consumption of hotel buildings in Thailand
รหัสดีโอไอ
Creator Siriluk Chiarakorn
Title Factors affecting electricity consumption of hotel buildings in Thailand
Contributor Suwajee Tangon, Jaruwan Chontanawat
Publisher Asia-Pacific Journal of Science and Technology
Publication Year 2561
Journal Title Asia-Pacific Journal of Science and Technology
Journal Vol. 23
Journal No. 1
Page no. 1-11
Keyword Electricity Consumption Intensity, Factors, Hotel Buildings, Thailand
URL Website https://www.tci-thaijo.org/index.php/APST/index
Website title https://tci-thaijo.org/index.php/APST/article/view/112302
ISSN 2539-6293
Abstract This paper presents a study on energy performance of Thailand's hotel buildings. Energy consumption data, hotel characteristics and operational data were collected from 63 hotels through a technical survey. The annual Electricity Consumption Intensities (ECI) of the sampled hotels were then calculated and the parameters affecting electricity consumption of the hotels were analyzed using Pearson correlation. Results indicated that most of the sampled hotels in Thailand consumed electricity, liquefied petroleum gas (LPG) and diesel fuel. Electricity was the primary energy source, accounting for 69% to 94% of the consumption in various hotels. Electricity was mainly used in air conditioning (57%), followed by lighting (18%), escalators (9%), water heating (8%), and fans and pumps (8%). The average annual ECIs of hotel buildings in Thailand were 321.84 kWh/m2, 35,210.40 kWh/guest room and 2,292.36 kWh/room night. Pearson correlations showed that worker density had a positive correlation with the monthly ECI in kWh/m2 with a 99% confidence level, whereas Occupancy Rates (OR) had a negative correlation with the monthly ECI in kWh/room night at a 95% confidence level. A predictive model was determined based on a stepwise linear regression. It indicated that the optimization of some hotel operational factors, such as the number of room nights, number of workers, worker density and OR could lead to significant decreases in electricity consumption in Thai hotel buildings.
Asia-Pacific Journal of Science and Technology

บรรณานุกรม

EndNote

APA

Chicago

MLA

ดิจิตอลไฟล์

Digital File
DOI Smart-Search
สวัสดีค่ะ ยินดีให้บริการสอบถาม และสืบค้นข้อมูลตัวระบุวัตถุดิจิทัล (ดีโอไอ) สำนักการวิจัยแห่งชาติ (วช.) ค่ะ