A study of flashover voltage of pin-post and line-post insulators under atmospheric conditions in Thailand
รหัสดีโอไอ
Title A study of flashover voltage of pin-post and line-post insulators under atmospheric conditions in Thailand
Creator Xaysomphone Kounlabout
Contributor Komson Petcharaks
Publisher Chulalongkorn University
Publication Year 2549
Keyword Gases, Dew point, Evaporation, Air pressure, Temperature, Saturation vapor pressure, ก๊าซ, ก๊าซ, การระเหย, ความดันไอแบบอิ่มตัว
Abstract The flashover voltage test results under laboratory atmospheric condition of external insulation are usually converted to the standard atmospheric condition by international or national standard. Thus, this thesis presents the study of the conversion of flashover voltage of Pin-post and Line-post insulator under atmospheric conditions in high voltage laboratory to standard atmospheric conditions recommended by international standard: IEC 60060-1:1989/IEEE4:1995, IEEE4 Amendment1 Std4a:2001 and national standard: ANSI C29:1 1988. For the high humidity of Thailand, the studies show that the humidity correction factor recommended by ANSI C29:1 1988 is suitable, while those recommended by IEC 600060-1: 1989 is appropriate only for negative impulse voltage. For positive impulse and AC voltage test according to IEC 60060-1: 1989, a new humidity correction factor is proposed.
URL Website cuir.car.chula.ac.th
Chulalongkorn University

บรรณานุกรม

EndNote

APA

Chicago

MLA

ดิจิตอลไฟล์

Digital File #1
Digital File #2
Digital File #3
Digital File #4
Digital File #5
Digital File #6
Digital File #7
DOI Smart-Search
สวัสดีค่ะ ยินดีให้บริการสอบถาม และสืบค้นข้อมูลตัวระบุวัตถุดิจิทัล (ดีโอไอ) สำนักการวิจัยแห่งชาติ (วช.) ค่ะ