The problem of cooling tower effect to energy loss in air conditioning system using chiller (Case study in the upper northeastern region)
รหัสดีโอไอ
Creator 1. W. Thanuanram
2. N. Auppapong
Title The problem of cooling tower effect to energy loss in air conditioning system using chiller (Case study in the upper northeastern region)
Publisher Thai Society of Mechanical Engineers (TSME)
Publication Year 2562
Journal Title Journal of Research and Applications in Mechanical Engineering (JRAME)
Journal Vol. 7
Journal No. 2
Page no. 154-160
Keyword Cooling tower, Problem, Energy conservation, Chiller
URL Website https://tci-thaijo.org/index.php/jrame/index
Website title Journal of Research and Applications in Mechanical Engineering (JRAME)
ISSN 2229-2152
Abstract This report presented energy loss in air conditioning systems due to inappropriate cooling towers. The samples were 32 buildings in the upper northeastern region of Thailand. We found that the 81 cooling towers in 32 buildings had less than 5 years runtime and the problems of inappropriate cooling towers can be classified into 4 groups of problems: problems of mismatch design, problems of low loaded fan, problems of water loss and problems of air leakage. The frequency share of the problems found were 37%, 34.7%, 10.9% and 17.4% respectively. From the study, this will increase the energy consumption of chillers about 720,049 kWh/year. During the project, some surveyed buildings had corrected some problems according to recommendations and can achieve energy saving of 318,870 kWh/year in total.
Journal of Research and Applications in Mechanical Engineering

บรรณานุกรม

EndNote

APA

Chicago

MLA

ดิจิตอลไฟล์

Digital File
DOI Smart-Search
สวัสดีค่ะ ยินดีให้บริการสอบถาม และสืบค้นข้อมูลตัวระบุวัตถุดิจิทัล (ดีโอไอ) สำนักการวิจัยแห่งชาติ (วช.) ค่ะ