Steady-state analysis of suitable interconnection pointsfor integration of offshore wind farms in the Gulf of Thailand |
---|---|
รหัสดีโอไอ | |
Creator | 1. Kusumal Chalermyanont 2. Phichet Ketsamee |
Title | Steady-state analysis of suitable interconnection pointsfor integration of offshore wind farms in the Gulf of Thailand |
Publisher | Research and Development Office, Prince of Songkla University |
Publication Year | 2564 |
Journal Title | Songklanakarin Journal of Science an Technology (SJST) |
Journal Vol. | 43 |
Journal No. | 6 |
Page no. | 1815-1822 |
Keyword | large-scale wind farm, interconnection point, fault currents, power flows, voltage stability, voltage variations, Gulf of Thailand |
URL Website | https://rdo.psu.ac.th/sjst/index.php |
ISSN | 0125-3395 |
Abstract | In Thailand, there is great potential for large-scale offshore wind farms in the Gulf of Thailand between Koh Tao andKoh Pha-Ngan, with possible installed capacity of up to 432 MW. The integration of large-scale wind farms will significantlyimpact the stability, security, quality, and operation of the power grid. In this paper, possible interconnection points to the 115-kV distribution grid system of the Provincial Electricity Authority (PEA) are selected for integrating three offshore wind farms.The steady-state analysis of power flows, voltage variations, voltage stability, and fault currents is performed using theDIgSILENT Power Factory program. The simulation results indicate appropriate interconnection points for offshore wind farmsto the 115-kV grid. These results will be important for developing offshore wind farms in Thailand. |